Regufoam® vibration 510 plus

Product Details

Standard forms of delivery, ex warehouse

PlatesThickness: 12.5 and 25 mm, special thicknesses on request
Length: 1,500 mm, special lengths available
Width: 1,000 mm
Stripping / smaler sizesOn request
Die-cutting, water-jet cutting, self-adhesive versions possible
Regufoam vibration 510 plus Vibration Isolation

Physical Data

Continuous static load0.22 N/mm²
Continuous and variable loads/operating load range0 to 0.32 N/mm²
Peak loads (rare, short-term loads)up to 4.0 N/mm²
Static modulus of elasticityBased on
EN 826
1.1 - 1.7N/mm²Tangential modulus, see figure “Modulus of elasticity”*
Dynamic modulus of elasticityBased on
DIN 53513
2.2 - 3.7N/mm²Depending on frequency, load and thickness, see figure “dynamic stiffness“*
Mechanical loss factorDIN 535130.15[-]Load-, amplitude- and frequency-dependent
Compression setBased on
DIN EN ISO 1856
4.2%Measured 30 minutes after decompression with 50% deformation / 23 °C after 72 hrs
Tensile strengthBased on
DIN EN ISO 1798
2.4N/mm²
Elongation at breakBased on
DIN EN ISO 1798
240%
Tear resistanceBased on
DIN ISO 34-1
9.3N/mm
Fire behaviourDIN 4102
DIN EN 13501
B2
E
[-]
[-]
Normal flammability
Sliding frictionBSW-laboratory
BSW-laboratory
0.7
0.8
[-]
[-]
Steel (dry)
Concrete (dry)
Compression hardnessBased on
DIN EN ISO 3386-2
330kPaCompressive stress at 25 % deformation
test specimen h = 25 mm
Rebound elasticityBased on
DIN EN ISO 8307
60%dependent on thickness,
test specimen h = 25 mm
Force reductionDIN EN 1490461%dependent on thickness,
test specimen h = 25 mm

* The technical data sheets are available for download in the password protected area. Register here to get access.